Environment |
Ambient Operating
Temperature |
-10ºC to 40ºC @ 6kHz.
-10ºC to 50ºC @ 3kHz
For SE Size 4 (@ 18.5kW) and all SE Size 5's.
-10ºC to 40ºC @ 3kHz |
Cooling method |
Convection and forced convection, model dependent |
Humidity |
95% maximum non-condensing at 40ºC |
Storage Temperature |
-40ºC to 60ºC |
Altitude |
Derate the continuous output current by 1% for every 100m above
1000m to a maximum of 4000m. |
Vibration |
Tested in accordance with IEC 68-2-34 and IEC 68-2-36 |
Mechanical Shock |
Tested in accordance with IEC 68-2-29 |
Enclosure |
NEMA 1 (IP 21) |
Electromagnetic Immunity |
In compliance with EN61800-3 and EN50082-2 |
Electromagnetic Emissions |
In compliance with EN61800-3 second environment, without RFI
filter.
EN50081-1*, EN500821-2 and EN50081-3 first environment with optional
RFI filter. *Size 1 only |
|
|
AC Supply Requirements |
Voltage |
200V model: 200 to 240 VAC ±10%
400V model: 380 to 480 VAC ±10% |
Phase |
1ph and 3ph (Model dependent) |
Maximum Supply Imbalance |
2% negative phase sequence (3% voltage imbalance between phases) |
Frequency |
48 to 62 Hz |
Input Displacement Power Factor |
0.97 |
|
|
Control |
Switching Frequency |
3, 6 and 12 kHz (Default value model dependent) |
Output Frequency |
Up to 1000 Hz |
Frequency Accuracy |
±0.01% of full scale |
Frequency Resolution |
0.1Hz |
Analog Input Resolution |
10 Bit + sign (Qty 2) |
Serial Communications |
ANSI 2-wire EIA485 via RJ45 connector. Baud rate is 4800, 9600 or
19,200 |
Braking |
DC injection braking standard.
Dynamic braking transistor standard (not available on Size 1) |
|
|
Protection |
DC Bus Under-voltage Trip |
200V model: 180 VDC |
(approx 127 VAC line voltage) |
400V model: 400 VDC |
(approx 282 VAC line voltage) |
DC Bus Overvoltage Trip |
200V model: 420 VDC |
(approx 299 VAC line voltage) |
400V model: 830 VDC |
(approx 587 VAC line voltage) |
MOV Voltage Transient Protection |
160 Joules, 1400 VDC clamping (Line to line and line to earth) |
Drive Overload Trip |
Current overload value is exceeded.
Programmable to allow up to 150% of drive current for one minute |
Instantaneous Over-current Trip |
215% of drive rated current |
Phase Loss Trip |
DC bus ripple threshold exceeded |
Over-temperature Trip |
Drive heatsink temperature exceeds 95°C (203ºF) |
Short Circuit Trip |
Protects against output phase to phase fault |
Earth Fault Trip |
Protects against output phase to earth fault |
Motor Thermal Trip |
Electronically protects the motor from overheating due to loading
conditions |
|
|
Approvals & Listings |
UL, cUL |
UL File Listed 8D14 |
IEC |
Meets IEC Vibration, Mechanical Shock and Electromagnetic
Immunity Standards |
CE |
Designed for marking |
NEMA |
NEMA 1 enclosure type |
ISO 9002 |
Certified Manufacturing Facility |
ISO 14001 |
Certified Manufacturing Facility |