SM-I/O PELV Termination
Option Module |
Colour |
Name |
17 Way Terminal |

|
Turquoise
blue |
SM-I/O PELV |
Orange |
17 way Terminal |
|
|
Description |
1 |
|
|
0V common |
2 |
|
|
+24V input |
3 |
|
|
Digital I/O 1 |
4 |
|
|
Digital I/O 2 |
5 |
|
|
Digital I/O 3 |
6 |
|
|
Digital I/O 4 |
7 |
|
|
Digital input 5 |
8 |
|
|
Analogue input 1
non-inverting input |
9 |
|
|
Analogue input 1
inverting input |
10 |
|
|
Analogue output 1 |
11 |
|
|
0V common |
12 |
|
|
Analogue output 2 |
13 |
|
|
0V common |
14 |
|
|
Relay 1 contact 1 |
15 |
|
|
Relay 1 contact 2 |
16 |
|
|
Relay 2 contact 1 |
17 |
|
|
Relay 2 contact 2 |
Features
The SM-I/O PELV is designed to meet the I/O requirements
of chemical and similar industries. The Solutions Module provides additional
galvanic isolation to that within the drive itself. The requirements of PELV
(Protective Extra Low Voltage) according to IEC 61800-5-1, and Namur NE37are
met.
All terminals on the SM-I/O PELV have the following
provisions for electrical safety:
- Decisive voltage class A according to IEC 61800-5-1, i.e. less than
30Vac r.m.s., 42.4Vac peak, 60Vdc mean
- Protective separation from live parts, comprising supplementary
insulation in conjunction with the basic insulation of the drive control
circuits, suitable for all supply voltages and configurations for which
the drive is intended.
The PELV circuit is permitted to be grounded. This
connection must be made externally if required.
Note that PELV circuits do not require protection against contact, but this
applies only when used within a zone of equipotential bonding. For further
guidance on safety requirements and PELV consult the relevant electrical
safety code for the region where the Solutions Module will be used.
The SM-I/O PELV can be used on the following products:
The SM-I/O PELV increases the I/O capability of the drive by adding the
following to the existing I/O:
- 2 x Analogue current outputs
- 1 x Analogue current input
- 4 x Digital inputs/outputs
- 1 x Digital input
- 2 x Relays (30Vdc contact rating)
All connections from the Solutions Module to the drive are
made via the drive connector.
Connections from external equipment to the 24V voltage input, relays,
digital and analogue I/O are made via a 17-way pluggable screw connector.
On the Unidrive SP a total of three SM-I/O PELV modules can be fitted at any
one time. On the Commander SK only one can be fitted.
|